Indonesia
English

Precision Electro Pneumatic Transducers RT Series



Download PDF (1.661,6 Kb)

・With the use of incorporated Floating system , RT Series Transducers reduce a supply pressure to a regulated Output pressure which is directly proportional to an Electric Input Signal.
Available in Model RT・I/P

・Highly accurate control of air pressure.
Linearity ( 1.0 to 1.5 % ) F.S.
Hysteresis ≦ ±1.0% F.S

・Outstanding low supply pressure Sensitivity.
Output pressure is virtually unaffected (≦ ±0.5 % F.S ) by variations in supply
pressure.

・Large Flow Rate allows direct drive of pneumatic control devices.

・Field Reversible.

・Excellent Repeatability
Normal load ≦ 2.5 % F.S.
Intermittent load ≦ 0.5 % F.S.

・Wide Adjustment Range.
Span Adjust Range :
Model RT・E/P-8-2 0.65 to 0.82 MPa
Model RT・I /P-8-2 0.24 to 0.82 MPa

・Mounts at Any Angle.
Zero/Span Readjustment required.

・Small size permits use in restricted areas.

・Principal Dimensions □54×105


Specifications
Model RT・E/P-8-2 RT・I/P-8-2 RT・I/P-1-2
Working Fluid Clean Compressed Air
Set Pressure Range MPa 0.02~0.82 0.02~0.1
Input signal Control System Voltage (2-line) Current (2-Wire)
Voltage VDC 0~10
Impedance Ω 805
current mADC 4~20
Impedance Ω 260 180
Linearity %.F.S 1.5 1.0
Hysteresis %.F.S 1.0
Repeatability %.F.S ±0.1 ±0.5
Step Response sec 1.0 0.2
Span Adjust Range MPa 0.65 to 0.82 0.24 to 0.82
Relief Sensitivity MPa Set Pressure Range+0.001以下
Air Consumption Nl/min 3.7 以下 4.8 以下
Range of Working Temperature ℃ 5 ~ 60
Pipe Port Rc(PT) 1/4
Gauge Port Rc(PT) 1/4
mounting Bracket (Standard)
Weight kg 0.94


Ordering Information
RT E/P 8 2 G025







Input Signal Set Pressure Range option
(Pressure gauge)
E/P Voltage Conversion System 1 0~0.1MPa G025 0~0.025MPa
I/P Current Conversion System 8 0~ 0.82MPa G060 0~0.6MPa


G010 0~1MPa